摘要

为了保证电力系统在风荷载作用下安全稳定运营,建立准确的输电线舞动模型面临巨大挑战。本研究以复杂线路中的覆冰四分裂导线为研究对象,采用数据驱动稀疏识别算法重建舞动模型。首先,推导了覆冰四分裂导线舞动的理论模型;然后,基于非线性动力学稀疏识别(SINDy)算法重建舞动模型;最后,通过具体算例来研究不同噪声幅值下舞动模型的重建精度。结果表明:在无噪声测量数据下,SINDy算法准确地恢复了舞动模型的结构及参数;通过对舞动模型进行灵敏度分析,发现随着噪声幅值的增大,三次项的系数均值误差较一次项大;在噪声幅值为0.1以内时,重建模型位移时程的决定系数在0.93以上,其中噪声幅值为0.05时,决定系数高达0.97。此外,该算法仅需少量数据即可达到很高的模型重建精度。研究成果对验证防舞设计及制定防舞计划具有重要作用。

Abstract

To ensure the safe and stable operation of the power system under the action of wind loads, it is a huge challenge to establish an accurate transmission line galloping model. In this paper, taking the iced quad bundle conductors in complex lines as the research object, a data-driven sparse identification algorithm is used to reconstruct the galloping model. First, the theoretical galloping model of the iced quad bundle conductors is derived. Then, the galloping model is reconstructed based on the sparse identification of nonlinear dynamics (SINDy) algorithm. Last, the reconstruction accuracy of the galloping model under different noise amplitudes is studied through specific examples. The results show that under the noise-free measurement data, the SINDy algorithm can accurately restore the structure and parameters of the galloping model. By sensitivity analysis of the galloping model, with the increase of the noise amplitude, the coefficient mean error of the cubic term is larger than the coefficient mean error of the first term. When the noise amplitude is within 0.1, the determination coefficient of the displacement time history of the reconstructed model is above 0.93. Meanwhile, when the noise amplitude is 0.05, the determination coefficient is as high as 0.97. Furthermore, the algorithm achieves high model reconstruction accuracy with only a small amount of data. The research results play an important role in verifying anti-galloping design and formulating anti-galloping plans.

关键词

覆冰导线 / 数据驱动 / 稀疏识别 / 舞动方程 / 四分裂

Key words

iced conductor / data-driven / sparse identification / galloping equation / quad bundle

引用本文

引用格式 ▾
刘小会,陈黎兵,杨军,赵建坤,安东. 基于数据驱动的输电线舞动模型的重建[J]. 应用力学学报, 2026, 43(1): 68-78 DOI:10.11776/j.issn.1000-4939.2026.01.006

登录浏览全文

4963

注册一个新账户 忘记密码

参考文献

[1]

LOU W J, WANG J W, CHEN Y, et al. Effect of motion path of downburst on wind-induced conductor swing in transmission line[J]. Wind and structures, 2016, 23(3): 211-229.

[2]

LIU X H, HU Y, CAI M Q. Free vibration analysis of transmission lines based on the dynamic stiffness method[J]. Royal Society Open Science, 2019, 6(3): 181354.

[3]

DEN HARTOG J P. Transmission line vibration due to sleet[J]. Transactions of the American Institute of Electrical Engineers, 1932, 51(4): 1074-1076.

[4]

NIGOL O, BUCHAN P G. Conductor galloping-part II torsional mechanism[J]. IEEE transactions on power apparatus and systems, 1981, PAS-100(2): 708-720.

[5]

YU P, SHAH A H, POPPLEWELL N. Inertially coupled galloping of iced conductors[J]. Journal of applied mechanics, 1992, 59(1): 140-145.

[6]

CAI M Q, YAN B, LU X, et al. Numerical simulation of aerodynamic coefficients of iced-quad bundle conductors[J]. IEEE transactions on power delivery, 2015, 30(4): 1669-1676.

[7]

LU J Z, WANG Q, WANG L M, et al. Study on wind tunnel test and galloping of iced quad bundle conductor[J]. Cold regions science and technology, 2019, 160: 273-287.

[8]

MATSUMIYA H, YAGI T, MACDONALD J H G. Unsteady aerodynamic force modelling for 3-DoF-galloping of four-bundled conductors[J]. Journal of fluids and structures, 2022, 112: 103581.

[9]

XIONG W, YUAN H J, YOU L. Prediction method of icing thickness of transmission line based on MEAO[J]. Cluster computing, 2018, 21(1): 845-853.

[10]

张博, 陶亚光, 常帅帅, 等. MEMS传感器输电线路舞动轨迹监测[J]. 中国测试, 2022, 48(1): 53-59.

[11]

ZHANG Bo, TAO Yaguang, CHANG Shuaishuai, et al. Transmission line galloping trajectory monitoring based on MEMS sensor[J]. China measurement & test, 2022, 48(1): 53-59(in Chinese).

[12]

ZOU H B, LU M. Developing high-frequency fiber bragg grating acceleration sensors to monitor transmission line galloping[J]. IEEE access, 2021, 9: 30893-30897.

[13]

刘辉, 马增泰, 林济铿. 覆冰导线舞动方程的建立及求解策略[J]. 中国电力, 2021, 54(7): 67-75.

[14]

LIU Hui, MA Zengtai, LIN Jikeng. Establishment and solution strategy of galloping equation of iced conductors[J]. Electric power, 2021, 54(7): 67-75(in Chinese).

[15]

曹海林, 陶璐, 蔡文斌, 等. 弧长约束下基于分布式倾角信息的输电线舞动曲线重建[J]. 高电压技术, 2018, 44(5): 1535-1541.

[16]

CAO Hailin, TAO Lu, CAI Wenbin, et al. Transmission line galloping curve reconstruction based on distributed inclination information and arc-length constraint[J]. High voltage engineering, 2018, 44(5): 1535-1541(in Chinese).

[17]

谢东升, 孙滔, 史卓鹏, 等. 基于三维重建的输电线舞动检测方法研究[J]. 国外电子测量技术, 2022, 41(3): 96-101.

[18]

XIE Dongsheng, SUN Tao, SHI Zhuopeng, et al. Research on galloping detection method of transmission line based on three-dimensional reconstruction[J]. Foreign electronic measurement technology, 2022, 41(3): 96-101(in Chinese).

[19]

WU D C, CAO H L, LI D, et al. Energy-Efficient reconstruction method for transmission lines galloping with conditional generative adversarial network[J]. IEEE access, 2020, 8: 17310-17319.

[20]

TIBSHIRANI R. Regression shrinkage and selection via the lasso[J]. Journal of the Royal Statistical Society: series b (methodological), 1996, 58(1): 267-288.

[21]

BRUNTON S L, PROCTOR J L, KUTZ J N. Discovering governing equations from data by sparse identification of nonlinear dynamical systems[J]. Proceedings of the National Academy of Sciences of the United States of America, 2016, 113(15): 3932-3937.

[22]

MANGAN N M, BRUNTON S L, PROCTOR J L, et al. Inferring biological networks by sparse identification of nonlinear dynamics[J]. IEEE transactions on molecular biological and multi-scale communications, 2016, 2(1): 52-63.

[23]

QUADE M, ABEL M, NATHAN KUTZ J, et al. Sparse identification of nonlinear dynamics for rapid model recovery[J]. Chaos, 2018, 28(6): 063116.

[24]

LI S W, KAISER E, LAIMA S J, et al. Discovering time-varying aerodynamics of a prototype bridge by sparse identification of nonlinear dynamical systems[J]. Physical review E, 2019, 100(2): 022220.

[25]

SHEA D E, BRUNTON S L, KUTZ J N. SINDy-BVP: sparse identification of nonlinear dynamics for boundary value problems[J]. Physical review research, 2021, 3(2): 023255.

[26]

ZHANG Q, POPPLEWELL N, SHAH A H. Galloping of bundle conductor[J]. Journal of sound and vibration, 2000, 234(1): 115-134.

[27]

闵光云, 刘小会, 严波, 等. 覆冰四分裂导线风洞试验与稳定性研究[J]. 力学与实践, 2020, 42(4): 447-454.

[28]

MIN Guangyun, LIU Xiaohui, YAN Bo, et al. Wind tunnel test and stability study of iced quad bundle conductor[J]. Mechanics in engineering, 2020, 42(4): 447-454(in Chinese).

[29]

IRVINE H M. Cable structures[M]. Cambridge: MIT Press, 1981.

[30]

DESAI Y M, YU P, POPPLEWELL N, et al. Finite element modelling of transmission line galloping[J]. Computers & structures, 1995, 57(3): 407-420.

[31]

BRUNTON S L, KUTZ J N. Data-driven science and engineering: machine learning, dynamical systems, and control[M]. Cambridge: Cambridge University Press, 2022.

[32]

严波, 刘小会, 赵莉, 等. 存在内共振的覆冰四分裂导线的非线性舞动[J]. 应用数学和力学, 2014, 35(1): 39-49.

[33]

YAN Bo, LIU Xiaohui, ZHAO Li, et al. Nonlinear galloping of iced quad-bundle conductors with internal resonances[J]. Applied mathematics and mechanics, 2014, 35(1): 39-49(in Chinese).

基金资助

国家自然科学基金资助项目(51308570)

重庆市自然科学基金资助项目(cstc2021jcyj-msxmX0166)

AI Summary AI Mindmap
PDF (6870KB)

107

访问

0

被引

详细

导航
相关文章

AI思维导图

/

〈 〉