In response to the national “14th Five-Year Plan” to vigorously promote prefabricated construction and enhance the energy efficiency of new buildings and to contribute to the achievement of the nation's “dual carbon” target, a prefabricated structural insulation integrated composite sandwich wall panel is proposed. To achieve a fully dry connection for these wall panels, solid concrete frames are positioned around the perimeter of the panels as one of the connectors. The presence of concrete frames creates a significant thermal bridge, which largely determines the thermal performance of the wall panel. Quantifying the effect of the frame ratio on the thermal performance of the wall panel is of great guiding significance for its structural design optimization and practical engineering application. Therefore, six sets of wall panel specimens with varying frame ratios were designed and tested by calibrated hot box method in this study to quantitatively analyze the effect of the frame ratio on the thermal performance of prefabricated wall panels. The experimental results reveal that the presence of concrete frames not only postpones the time to reach a steady state in thermal transmission but significantly reduces the thermal performance of the wall panel. When the frame ratio is 19.94%, 30.85%, 40.95%, 50.26%, and 61.43%, the thermal resistance of the wall panel is reduced by 79.26%, 84.28%, 87.48%, 89.36%, and 91.10%, respectively. To meet the current building energy-saving requirements, the frame ratio of the wall panel should be controlled within 20% in practical engineering applications. Through a comparative analysis of various methods for calculating wall panel thermal resistance with experimental results, it is recommended to use the zone method as the thermal resistance calculation method for wall panels with concrete frames.
按照1.6节进行标定试验,并记录标定试验过程中计量箱加热功率和各热流测点处的热流值,取试验结束前24 h内记录数据的平均值作为标定试件稳态时的计算指标.结果表明,热传递达到稳态时,计量箱加热功率为10.05 W,由各测点热流值计算的面积加权平均热流值为6.67 W/m2,通过式(4)计算试验过程的热量损失为4.03 W.
China association of building energy efficiency, Institute urban-rural construction and development of Chongqing University. China building energy and carbon emissions report 2022[J].Construction and Architecture,2023(2):57-69.(in Chinese)
[3]
WUH R, ZHANGT. Multi-objective optimization of energy, visual, and thermal performance for building envelopes in China’s hot summer and cold winter climate zone[J]. Journal of Building Engineering, 2022, 59:105034.
YUJ H, YANGC Z, TIANL W,et al .Research on the optimum insulation thickness of the external wall for residential buildings in Changsha region[J].Journal of Hunan University (Natural Sciences), 2009, 36(9): 16-21.(in Chinese)
[6]
ZHAOZ G, YANGX S, QUX L,et al .Thermal insulation performance evaluation of autoclaved aerated concrete panels and sandwich panels based on temperature fields:experiments and simulations[J].Construction and Building Materials,2021,303:124560.
XIONGF, LOUG Y, RANM M. A bolted connection of precast concrete composite insulation sandwich panels and its preparation method: CN115126148A[P]. 2022-09-30. (in Chinese)
[9]
KOSNYJ, CHILDSP, DESJARLAISA. Thermal performance of prefabricated concrete sandwich wall panels[R]. Oak Ridge, TN: Oak Ridge National Laboratory Building Technology Center, 1999.
[10]
O’HEGARTYR, KINNANEO .Review of precast concrete sandwich panels and their innovations[J]. Construction and Building Materials,2020,233:117145.
[11]
ŠADAUSKIENĖJ, RAMANAUSKASJ, ŠEDUIKYTĖL, et al. A simplified methodology for evaluating the impact of point thermal bridges on the high-energy performance of a passive house[J]. Sustainability, 2015, 7(12):16687-16702.
[12]
LEEB J, PESSIKIS .Revised zone method R-value calculation for precast concrete sandwich panels containing metal wythe connectors[J].PCI Journal,2008,53(5):86-100.
[13]
YUS S, LIUY F, WANGD J, et al. Theoretical, experimental and numerical study on the influence of connectors on the thermal performance of precast concrete sandwich walls[J]. Journal of Building Engineering, 2022, 57:104886.
ZHUW X, XUJ F, WUZ M, et al. Simulation and calculation analysis of thermal performance of prefabricated concrete sandwich wall panels[J]. Concrete,2020(3):128-131.(in Chinese)
[16]
LIUP, LUOX Y, CHENY, et al. Thermodynamic and acoustic behaviors of prefabricated composite wall panel[J]. Structures, 2020, 28:1301-1313.
[17]
KIMY J, ALLARDA. Thermal response of precast concrete sandwich walls with various steel connectors for architectural buildings in cold regions[J]. Energy & Buildings, 2014, 80:137-148.
[18]
WOLTMANG, NOELM, FAM A. Experimental and numerical investigations of thermal properties of insulated concrete sandwich panels with fiberglass shear connectors[J]. Energy & Buildings, 2017, 145: 22-31.
[19]
ABEDINIANGERABIB, SHAHANDASHTIS M, BELLB, et al. Building energy performance analysis of ultra-high-performance fiber-reinforced concrete (UHP-FRC) façade systems[J]. Energy & Buildings, 2018, 174:262-275.
BAIZ X, GAOJ W, LIUX C, et al. Research on the connection performance of glassfiber reinforced plastics connector of sandwich wall[J]. Industrial Construction, 2020, 50(2):169-176.(in Chinese)
[22]
DINGY G, SONGZ J, CHENK W,et al .Thermal insulation performance and reliability of the “structure-insulation” integrated wall panel (SIW) for storage grain bungalows[J].Buildings,2022, 12(9):1306.
[23]
ZHAIX M, WANGY H, WANGX M .Thermal performance of precast concrete sandwich walls with a novel hybrid connector[J].Energy & Buildings,2018,166:109-121.
JIANGH Z. Research on behavior of precast concrete sandwich panels with steel-GFRP composite connectors[D]. Nanjing: Southeast University, 2019:139-157. (in Chinese)
[26]
LEEB, PESSIKIS. Analytical investigation of thermal performance of precast concrete three-wythe sandwich wall panels[J]. PCI Journal, 2004, 49(4):88-101.
[27]
LEEB, PESSIKIS. Thermal performance evaluation of precast concrete three-wythe sandwich wall panels[J]. Energy & Buildings, 2006, 38(8):1006-1014.
[28]
BIDAS M, ABDUL AZIZF N A, JAAFARM S,et al .Thermal resistance of insulated precast concrete sandwich panels[J].International Journal of Concrete Structures and Materials, 2021,15(1): 695-706.
HAOJ F, SUNJ G, TENGZ C,et al .Study on the compound wallboard mechanics and thermo engineering performance design of countryside energy-saving residence[J].Science Technology and Engineering,2009,9(23):7210-7213.(in Chinese)
[31]
ZHANGZ J, CHENJ X, ELBASHIRYE M A, et al. Effects of changes in the structural parameters of bionic straw sandwich concrete beetle elytron plates on their mechanical and thermal insulation properties[J]. Journal of the Mechanical Behavior of Biomedical Materials, 2019, 90:217-225.
[32]
VOELLINGERT, BASSIA, HEITELM .Facilitating the incorporation of VIP into precast concrete sandwich panels[J].Energy & Buildings,2014,85:666-671.
[33]
O'HEGARTYR, REILLYA, WESTR, et al. Thermal investigation of thin precast concrete sandwich panels[J]. Journal of Building Engineering, 2020, 27:100937.
[34]
KLÕŠEIKOP, PIIRR, JELTSOVM,et al .Thermal bridge effect of vertical diagonal tie connectors in precast concrete sandwich panels:an experimental and computational study[J].E3S Web of Conferences,2020,172:08001.
ZHUW X, XUJ F, WUZ M,et al. Optimization and design suggestion of thermal performance of prefabricated concrete sandwich insulation wall panel[J]. Concrete,2021(1):132-134.(in Chinese)
[37]
YUS S, LIUY F, WANGD J,et al .Review of thermal and environmental performance of prefabricated buildings:implications to emission reductions in China[J].Renewable and Sustainable Energy Reviews,2021,137:110472.
Thermal insulation-determination of steady-state thermal transmission properties-calibrated and guard hot box:GB/T 13475—2008 [S]. Beijing:Standards Press of China, 2009: 1-10.(in Chinese)
General code for energy efficiency and renewable energy application in buildings:GB 55015—2021 [S]. Beijing: China Architecture & Building Press, 2021:4-9. (in Chinese)
[46]
ASHRAE handbook: fundamentals [S]. Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2009.