Objective Offshore wind power development increasingly relies on voltage source converter-based high-voltage direct current (VSC‒HVDC) transmission to accommodate large power capacities over long distances. However, dynamic interactions between wind turbine generators and VSC‒HVDC systems can induce oscillations, as demonstrated by incidents such as the 2014 resonance accident in the German North Sea and similar oscillation events in Chinese wind power projects. In this study, we aimed to address small-signal stability (SSS) issues in these systems by deriving analytical criteria to characterize the interactions between permanent magnet synchronous generators (PMSG) and VSC‒HVDC systems and provide a simpler approach to SSS assessment. Methods The SSS of the PMSG-based wind farm connected to the VSC‒HVDC system was evaluated using an SSS criterion. At the direct current (DC) voltage dynamic timescale, the PMSG model retained the low-frequency phase-locked loop (PLL) and the DC voltage control outer loop of the grid-side converter, whereas the VSC‒HVDC model retained its alternate current (AC) voltage control outer loop. All PMSGs in the PMSG-based wind farm subsystem were assumed to exhibit identical dynamic characteristics. Based on this assumption, reduced-order models of the PMSG-based wind farm subsystem and the VSC‒HVDC subsystem were derived. Then, a reduced-order model of the entire system was developed. The coefficients of the characteristic equation of the reduced-order model were expressed in terms of the line connection reactance and PMSG output active power. The Routh-Hurwitz stability criterion was then applied to derive the SSS criteria associated with the line connection reactance and PMSG output active power. These criteria simplified the SSS assessment process by explaining why increased PMSG output power or weaker grid connections increased the risk of instability. The SSS criteria were established as follows: 1) Criterion 1: At a fixed line connection reactance xL, the system’s SSS depended on the maximum allowable active power output tP0 of the PMSG. Higher PMSG output power increased the risk of instability. 2) Criterion 2: At a fixed PMSG output active power Pg0, the system’s SSS depended on the maximum allowable line reactance tL0. Greater line reactance increased the likelihood of instability. tL0 and tP0 were determined as the smallest positive real roots that satisfied all inequalities of the Routh-Hurwitz stability criterion for the reduced-order model. We identified three primary factors that contributed to small-signal instability in a PMSG-based wind farm connected to the VSC‒HVDC system: 1) PMSG output active power, 2) line connection reactance, and 3) control parameters of the PMSG and VSC‒HVDC. The high order of the PMSG dynamic model increased the complexity of the full-order system model and presented challenges for theoretical analysis. Simulation and numerical results confirmed the validity of the proposed criteria. Results and Discussions The validity of the derived SSS criteria was evaluated through two case studies. Case 1: The criteria were verified for a single PMSG connected to the VSC‒HVDC system under two scenarios. Scenario 1.1: At a fixed-line connection reactance of xL = 0.50 p.u., the influence of PMSG output active power on the system’s SSS was investigated. The maximum PMSG output active power that satisfied the SSS criterion was calculated as tP0 = 0.58. For verification, the PMSG output active power was gradually increased from 0.50 to 0.60 p.u., and the dominant oscillation modes were calculated using the full-order and reduced-order models. At Pg0 = 0.58, the eigenvalues of the full-order and reduced-order models were 0.120 ± j31.180 and 0.023 ± j31.170, respectively. The results demonstrated that the system became unstable when Pg0 > 0.58 p.u. Scenario 1.2: At a fixed PMSG output active power of Pg0 = 0.65 p.u., the influence of line connection reactance on SSS was examined. The maximum line connection reactance that satisfied the SSS criterion was calculated as tL0 = 0.47. For verification, the line connection reactance was increased from 0.40 to 0.50 p.u., and the dominant oscillation modes were calculated using both models. At xL = 0.47, the eigenvalues of the full-order and reduced-order models were 0.14 ± j31.21 and 0.035 ± j31.34, respectively. The results indicated that the system became unstable when xL > 0.47. Case 2: The criteria were validated for a wind farm comprising 15 PMSGs connected to the VSC‒HVDC system under two scenarios. Scenario 2.1: At a fixed line connection reactance of xL = 0.12 p.u., the effect of PMSG output active power on the system’s SSS was investigated. The maximum output power that satisfied the SSS criterion was calculated as tP0 = 0.155. For verification, the PMSG output active power was increased from 0.150 to 0.157 p.u., and the dominant oscillation modes were calculated. At Pg0 = 0.157, the eigenvalues of the full-order and reduced-order models were 0.160 ± j36.690 and 0.049 ± j36.870, respectively. The results demonstrated that the system became unstable when Pg0 > 0.155 p.u. Scenario 2.2: At a fixed PMSG output active power of Pg0 = 0.150 p.u., the influence of line connection reactance on the system’s SSS was analyzed. The maximum line connection reactance that satisfies the SSS criterion was calculated as tL0 = 0.138. For verification, the line connection reactance was increased from 0.130 to 0.140 p.u., and the dominant oscillation modes were calculated. At xL = 0.138, the eigenvalues of the full-order and reduced-order models were 0.163 ± j35.61 and 0.043 ± j36.080, respectively. The results indicated that the system became unstable when xL > 0.138. Conclusions The analytical criteria derived in this study provide an efficient approach for assessing the SSS of the PMSG-based wind farm connected to the VSC‒HVDC system. The findings of this study enhance the understanding of the mechanisms leading to oscillatory instability by revealing the relationships among key factors, such as the control parameters of PMSGs and VSC‒HVDC, PMSG output active power, and line connection reactance. The criteria provide a significant reduction in computational complexity, clear physical insights, and practical guidance for optimizing control parameters to maintain stability. The results demonstrate that adjusting parameters such as the PMSG’s DC voltage control loop, PLL settings, and the VSC‒HVDC’s AC voltage control loop can effectively improve system stability, even under high output power or weak grid connection conditions. Future research will extend these findings by investigating SSS in systems where wind farms are connected to a modular multilevel converter-based HVDC system.
近年来,海上风电得到迅速发展[1]。由于其具有传输功率大、传输距离远等特点,采用基于电压源换流器的柔性直流(voltage source converter based high voltage direct current,VSC‒HVDC)输电成为输送海上风电的有效方法[2]。由于风机换流器与柔直换流器之间易发生动态交互,可能引发系统振荡失稳。例如,2014年德国北海的海上风电场经高压VSC‒HVDC送出工程出现谐振事故[3],导致大量设备损坏,系统停运半年;国内南澳风电柔直工程出现过20~30 Hz次同步振荡[4‒5],张北新能源柔直工程出现过2~6 Hz次同步振荡[6]和750~3 550 Hz中高频振荡[7],如东海上风电柔直工程出现过320、2 000和2 500 Hz中高频振荡[8‒9]等。同时,直驱永磁同步发电机(permanent magnet synchronous generator,PMSG)凭借结构简单、效率高等优点,适用于海上发电[10]。根据是否考虑模块化多电平换流器(modular multilevel converter,MMC)内部动态,MMC可归纳为基于VSC‒HVDC模型和基于MMC‒HVDC模型的分析研究。其中,基于VSC‒HVDC模型的分析侧重于揭示VSC‒HVDC与风电机组控制之间的交互特性,而基于MMC‒HVDC模型的分析方法则侧重于揭示MMC内部动态对系统稳定性的影响。因此,本文重点研究直驱风电场经VSC‒HVDC并网系统中,PMSG与VSC‒HVDC动态交互作用引发的小信号稳定性问题。
直驱风电场经VSC‒HVDC并网系统的结构如图1所示,系统可分为直驱风电场子系统和VSC‒HVDC子系统。图1中,和分别为公共x‒y坐标系下直驱风电场的公共连接点(point of common coupling,PCC)电压和VSC‒HVDC整流侧的端电压;xL为线路连接电抗;X为VSC‒HVDC交流滤波电抗;Rdc和Ldc分别为直流输电线路的电阻和电抗;Cdc为VSC‒HVDC直流电容;Udc和Udc1分别为直流侧电压和VSC‒HVDC直流侧电压;Pr为直驱风电场向VSC‒HVDC传输的有功功率;Ir为直驱风电场子系统与VSC‒HVDC子系统之间的电流;r为风电场侧与VSC‒HVDC整流站之间的公共连接点;idc为VSC‒HVDC子系统直流侧的电流。直驱风电场中PMSG的详细全阶模型参见文献[12]。
式中: Uk 、 Ik 分别为第k台PMSG的端电压向量和输出电流向量,且 Uk =[UkxUky ]T, Ik =[IkxIky ]T,其中Ukx +jUky 、Ikx +jIky 分别为交流电网公共x‒y坐标系下第k台PMSG的端电压复数值和输出电流复数值;N为风电场内PMSG总台数; Xk 为降阶模型状态变量的列向量,且 Xk =[Udckxvkxpkθpk ]T; Ak 、 Bk 和 Ck 分别为第k台PMSG降阶模型的状态矩阵、输入矩阵和输出矩阵。用( Ak, Bk, Ck )表示第k台PMSG降阶模型的线性化状态空间模型,具体表达式如附录A式(A1)所示。
式中:为风电场网络的节点阻抗矩阵; Xn= Xw+ XL为网络电抗矩阵,其中 Xw为风电场场内线路电抗矩阵,矩阵 Xw中各元素xij,(i=1,2,…,N;j=1,2,…,N)的形成原则可参考文献[29], XL为风电场到VSC‒HVDC公共连接点的连接电抗矩阵,; E 为二维单位矩阵, E =[0 -1;1 0];⊗表示克罗劳内乘积。
直驱风电场的线路连接电抗通常远大于直驱风电场内部网络线路的电抗,因此 Xn通常由 XL主导,即:
假设λi (i=1,2,…,N)为矩阵 Xn的特征值, vi =[v1iv2i … vNi ]T为对应的特征向量。由于 Xn为实对称矩阵,可得 V--1= VT,其中 V 为矩阵 Xn全部特征向量构成的特征向量矩阵, V =[ v1v2 … vN ]∈R N×N。因此,可得:
式中,diag[λi ]表示对角元素为λi 的对角矩阵。
然后,引入以下状态变量向量变换,即:
式中:Δ X =[Δ X1 Δ X2 … Δ XN ]; Vn = V ⊗ En, En 为n×n的单位矩阵,n为单台PMSG线性化模型的阶数;为模态变换后状态向量; V2= V ⊗ E2, E2=[1 0;0 1]; U 为直驱风电场子系统中所有PMSG端电压的列向量,且; I 为直驱风电场子系统中所有PMSG输出电流构成的列向量,且 I =;∈R2N×1; IT= ∈R2N×1。
CaiXu, YangRenxin, ZhouJianqiao,et al.Review on offshore wind power integration via DC transmission[J].Automation of Electric Power Systems,2021,45(21):2‒22. doi:10.7500/AEPS20210909007
WangXifan, WeiXiaohui, NingLianhui,et al.Integration techniques and transmission schemes for off-shore wind farms[J]. Proceedings of the CSEE,2014,34(31):5459‒5466.
BuchhagenC, GreveM, MenzeA,et al.Harmonic stability—practical experience of a TSO[C]//Proceedings of the 15th Wind Integration Workshop.Darmstadt:Energynautics GmbH,2016:1‒6.
[6]
JingLyu, DongPeng, ShiGang,et al.Subsynchronous oscillation and its mitigation of MMC-based HVDC with large doubly-fed induction generator-based wind farm integration[J].Proceedings of the CSEE,2015,35(19):4852‒4860.
JingLyu, CaiXu, ZhangZhankui,et al.Impedance modeling and stability analysis of MMC-based HVDC for offshore wind farms[J].Proceedings of the CSEE,2016,36(14):3771‒3780.
LiHaozhi, XieXiaorong, LiuRuitong,et al.Analysis and mitigation of the subsynchronous oscillation in renewable energy system connected to the MMC‒HVDC[J].Proceedings of the CSEE,2024,44(8):2945‒2954.
GaoLei, JingLyu, CaiXu.Analysis of mid-frequency oscillation characteristics in Rudong MMC‒HVDC system for offshore wind farms[J].Power System Technology,2023,47(9):3495‒3506.
ZhaoZheng, LiMing, TianYuanyuan,et al.Resonance analysis and suppression in Jiangsu Rudong offshore wind power flexible DC system[J].Electric Power Construction,2023,44(6):144‒152.
HuangShoudao, RongFei.Power conversion and control of wind power system based on flexible DC transmission[M].Beijing:China Water & Power Press,2017.
[19]
黄守道,荣飞.基于柔性直流输电的风电系统功率变换与控制[M].北京:中国水利水电出版社,2017.
[20]
SunKun, YaoWei, ZhouYi,et al.Mechanism analysis and suppression of medium-frequency oscillation based on the SISO impedance in a PMSG-based wind farm when connected to a VSC‒HVDC[J].Proceedings of the CSEE,2023,43(2):442‒453.
WangYifan, ZhaoChengyong, GuoChunyi.Transfer function model and low-frequency stability analysis for PMSG-based wind farm interconnected with flexible-HVDC system[J].Proceedings of the CSEE,2020,40(5):1485‒1497.
LiuHanchao, SunJian.Voltage stability and control of offshore wind farms with AC collection and HVDC transmission[J].IEEE Journal of Emerging and Selected Topics in Power Electronics,2014,2(4):1181‒1189. doi:10.1109/jestpe.2014.2361290
[25]
YuJing, LinHongfei, WangXiao,et al.Mechanism analysis of near fundamental-frequency positive /negative-sequence oscillations in MMC‒HVDC connected direct-drive wind farm[J].Electric Power Construction,2024,45(2):10‒25.
ShaoBingbing, ZhaoZheng, XiaoQi,et al.Weak robustness analysis of close subsynchronous oscillation modes’ participation factors in multiple direct-drive wind turbines with the VSC‒HVDC system[J].Transactions of China Electrotechnical Society,2023,38(3):754‒769.
ShaoBingbing, ZhaoShuqiang, PeiJikun,et al.Subsynchronous oscillation characteristic analysis of grid-connected DDWFs via VSC‒HVDC system[J].Power System Technology,2019,43(9):3344‒3352.
ShaoBingbing, ZhaoShuqiang, GaoBenfeng,et al.Inside wind-farm/wind-farm-grid sub-synchronous oscillation characteristics analysis in multiple D‒PMSGs interfaced with VSC‒HVDC system[J].Proceedings of the CSEE,2020,40(12):3835‒3846.
ShaoBingbing, ZhaoShuqiang, YangYongheng,et al.Sub-synchronous oscillation characteristics and analysis of direct-drive wind farms with VSC‒HVDC systems[J].IEEE Transactions on Sustainable Energy,2021,12(2):1127‒1140. doi:10.1109/tste.2020.3035203
[34]
ShaoBingbing, ZhaoShuqiang, GaoBenfeng,et al.Adequacy of the single-generator equivalent model for stability analysis in wind farms with VSC‒HVDC systems[J].IEEE Transactions on Energy Conversion,2021,36(2):907‒918. doi:10.1109/tec.2020.3028546
[35]
WangYifan, ZhaoChengyong, GuoChunyi,et al.Dynamics and small signal stability analysis of PMSG-based wind farm with an MMC‒HVDC system[J].CSEE Journal of Power and Energy Systems,2020,6(1):226‒235.
[36]
WangYifan, ZhaoChengyong.Analysis of oscillation modes of a hybrid-based wind farm transmitted through MMC‒HVDC[J].Power System Protection and Control,2020,48(9):18‒26.
ZengQianqian, ZhuJianhang, HuJiabing,et al.Analysis of 6 Hz SSO caused by the interaction between wind turbines and MMC‒HVDC[C]//Proceedings of the 2023 IEEE 6th International Electrical and Energy Conference (CIEEC).Piscataway:IEEE,2023. doi:10.1109/cieec58067.2023.10167024
[39]
GaoBenfeng, LiuYangyang, WangXiao.Subsynchronous oscillation mechanism analysis of direct-drive wind farm with VSC‒HVDC system based on path analysis method[J].Proceedings of the CSEE,2023,43(17):6646‒6659.
GaoBenfeng, LiuYangyang, ShaoBingbing,et al.A path analysis method to study the subsynchronous oscillation mechanism in direct-drive wind farm with VSC‒HVDC system[J].International Journal of Electrical Power & Energy Systems,2022,142:108328. doi:10.1016/j.ijepes.2022.108328
[42]
WangDong, LiangLiang, ShiLei,et al.Analysis of modal resonance between PLL and DC‒link voltage control in weak-grid tied VSCs[J].IEEE Transactions on Power Systems,2019,34(2):1127‒1138. doi:10.1109/tpwrs.2018.2871616
[43]
YuanHao, YuanXiaoming, HuJiabing.Modeling of grid-connected VSCs for power system small-signal stability analysis in DC‒link voltage control timescale[J].IEEE Transactions on Power Systems,2017,32(5):3981‒3991. doi:10.1109/tpwrs.2017.2653939
[44]
HuangYunhui, ZhaiXuebing, HuJiabing, et al.Modeling and stability analysis of VSC internal voltage in DC‒link voltage control timescale[J].IEEE Journal of Emerging and Selected Topics in Power Electronics,2018,6(1):16‒28. doi:10.1109/jestpe.2017.2715224
[45]
DuWenjuan, DongWenkai, WangHaifeng,et al.Dynamic aggregation of same wind turbine generators in parallel connection for studying oscillation stability of a wind farm[J].IEEE Transactions on Power Systems,2019,34(6):4694‒4705. doi:10.1109/tpwrs.2019.2920413
[46]
DongWenkai, DuWenjuan, WangHaifeng.Dynamic equivalent model of a grid-connected wind farm for oscillation stability analysis[J].Proceedings of the CSEE,2021,41(1):75‒87.