Objective The gas-electric integrated energy system involves close coupling among power, natural gas, and cyber subsystems. The complexity and diversity of failure causes make system reliability assessment and optimization particularly challenging. In this study, we propose a multiobjective reliability optimization method for gas-electric integrated energy cyber-physical systems. Methods First, the effects of incorporating natural gas and cyber systems were evaluated based on traditional reliability indicators, and a set of reliability evaluation indicators was established. A correction factor was introduced to adjust the system’s failure rate and mean repair time to comprehensively account for the influence of the cyber system on the reliability of the gas-electric integrated energy system. Then, a multiobjective reliability optimization model was developed, in which two objective functions represented the penalty cost associated with the corrected failure rate and mean repair time and the generalized expected energy not supplied, respectively. Accordingly, the reliability optimization model for the gas-electric integrated energy cyber-physical system was solved using a nondominated sorting genetic algorithm, and its performance was compared to those of multiobjective genetic algorithms and multiobjective particle swarm optimization algorithms. Simulation-based verification was performed using an integrated gas-electric energy system comprising an 8-node power distribution network coupled with an 11-node natural gas system as a computational example. Finally, the system’s reliability was optimized under three scenarios involving cyber system failures, physical component damage, and cyber attacks, verifying the effectiveness of the proposed optimization method under different operating conditions. Results and Discussions Following the application of the NSGA‒Ⅱ multiobjective optimization algorithm, both optimization objectives decreased. Specifically, the penalty cost decreased by 12.42%, whereas the generalized expected energy not supplied decreased by 15.66%. In addition, the generalized system average interruption duration index (GSAIDI) decreased by 2.35%, whereas the generalized average service availability index (GASAI) exhibited minimal variation. The generalized system average interruption frequency index(GSAIFI) increased slightly, although the magnitude of this increase remained negligible. Under the cyber system failure scenario, the application of the NSGA‒Ⅱ optimization algorithm effectively mitigated the effects of system faults. Post-optimization analysis revealed substantial improvements in key reliability indicators: GSAIDI decreased by 9.28%, the penalty function decreased by 11.717%, and the generalized expected energy not supplied decreased by 18.143%. These quantitative improvements demonstrated that the proposed optimization method effectively enhanced system reliability during cyber system malfunctions. Following the destruction of the P2G coupling device and the gas turbine, all system reliability indicators increased, along with the average annual duration of energy supply shortages at each load point. Without the coupling device, the power and natural gas systems were no longer closely interconnected. The absence of energy conversion hubs between the two energy systems also resulted in severe energy supply shortages, which substantially compromised overall system reliability. These findings further demonstrated that the coupling device played a critical role in improving system reliability. Then, the NSGA‒Ⅱ optimization algorithm was applied to optimize the system, resulting in reductions in both objective functions. The average annual duration of energy supply shortages at the load points also decreased, which effectively mitigated the adverse effects of coupling device destruction on system reliability and demonstrated the effectiveness of the optimization algorithm under this scenario. Following the destruction of the gas source facility, the resulting failure interrupted the natural gas supply but may also have affected the energy supply of the power system through the gas-electric coupling device, increasing the risk of energy shortages throughout the integrated system. After the application of multiobjective optimization, the penalty function and the generalized system energy not supplied decreased, with F1 decreasing by 14.2%. These results indicated that the optimization algorithm effectively mitigated the effects of gas source failure on system reliability and further demonstrated the effectiveness of the proposed optimization method under this scenario. When power lines and gas pipelines were subjected to cyber attacks, both objective functions increased to varying degrees compared to the scenario without cyber attacks. Attacks targeting lines and pipelines located closer to power sources, gas sources, and coupling devices exerted more substantial effects on system reliability. However, following the application of the multiobjective optimization algorithm, both objective functions decreased, demonstrating the effectiveness of the proposed optimization method under cyber attack conditions. Conclusions The findings of the study indicate that establishing generalized system-level reliability metrics and applying the nondominated sorting genetic algorithm for multiobjective optimization of the gas-electric integrated energy cyber-physical system’s reliability successfully reduced both objective functions to a certain extent, improving overall system reliability. In addition, the algorithm was applied to various scenarios, including cyber system failures, physical component damage, and cyberattack impacts, and consistently improved system reliability across all scenarios. These results demonstrate the effectiveness of the proposed model and algorithm under various conditions.
综合能源系统(integrated energy system,IES)是一个融合了多种能源资源(如电力、热能、冷能、天然气、太阳能、风能等)和多个能源系统的复杂工程体系。其中,气电互联综合能源系统有效地实现了电力与天然气之间的高效互联与资源利用,推动了可再生能源的应用和发展,也有助于实现节能减排目标。然而,随着两个子系统耦合加强,系统间的交互作用增加了整体故障风险,小扰动事件可能引发大规模故障,如何确保系统可靠安全运行,成为需要关注的重点[1]。
ZhouBuxiang, MinXinwei, ZangTianlei,et al..Loss assessment and vulnerability analysis of an integrated electricity natural gas system under load redistribution attack[J].Advanced Engineering Sciences,2023,55(1):3‒13.
ZhouBuxiang, SunBinjie, ZangTianlei,et al.Security risk assessment approach for distribution network cyber physical systems considering cyber attack vulnerabilities[J].Entropy,2023,25(1):47. doi:10.3390/e25010047
[4]
DingMaosheng, WangHongru, WangChao,et al.Review of reliability assessments for energy Internet based on cyber physical integration[J].Power System Technology,2021,45(2):425‒436.
LiuZhaoxi, WeiWei, WangLingfeng,et al.An actuarial framework for power system reliability considering cybersecurity threats[J].IEEE Transactions on Power Systems,2021,36(2):851‒864. doi:10.1109/tpwrs.2020.3018701
[7]
ChenFan, ZhangJicong, ZhaoMeilian,et al.Operational reliability evaluation for power systems considering load redistribution attack[J].Power System Protection and Control,2023,51(8):160‒168.
LiXiao, XuJianbing, LiManli,et al.A security evaluation method for cyber physical distribution system considering influence of information failure[J].Electric Power,2022,55(2):73‒81.
ZhuBingquan, GuoYihao, GuoChuangxin,et al.A survey of the security assessment and security defense of a cyber physical power system under cyber failure threat[J].Power System Protection and Control,2021,49(1):178‒187.
BaoYingkai, GuoChuangxin, ZhangJinjiang,et al.Impact analysis of human factors on power system operation reliability[J].Journal of Modern Power Systems and Clean Energy,2018,6(1):27‒39. doi:10.1007/s40565-016-0231-6
[14]
LiuWenxia, YangYue, LiZhengzhou,et al.Reliability evaluation of integrated energy system considering multi-energy flow transmission and thermal inertia based on sequential simulation[J].Electric Power Automation Equipment,2020,40(7):10‒18.
ZhangDingmao, LiGengfeng, LiYiran,et al.An analytical method for reliability evaluation of distribution systems with multiple distributed generations under time-varying failure rates[J].Proceedings of the CSEE,2025,45(23):9075‒9088.
EajalA A, El‒AwadyA, El‒SaadanyE F,et al.A Bayesian approach to the reliability analysis of renewables-dominated islanded DC microgrids[J].IEEE Transactions on Power Systems,2021,36(5):4296‒4309. doi:10.1109/tpwrs.2021.3056314
[19]
KoeppelG, AnderssonG.Reliability modeling of multi-carrier energy systems[J].Energy,2009,34(3):235‒244.
[20]
GuimarãesI O, Leite da SilvaA M, NascimentoL C,et al.Reliability assessment of distribution grids with DG via quasi-sequential Monte Carlo simulation[J].Electric Power Systems Research,2024,229:110122. doi:10.1016/j.epsr.2024.110122
[21]
WeiYong, CuiJunbin, LiuXintong,et al.A reliability analysis method power system wide area protection communication system based on an improved dynamic fault tree[J].Power System Protection and Control,2021,49(23):171‒177.
XuDenghui, WangYanyan, ZhangYoubing,et al.Reliability assessment of active distribution network considering cyber failure in uncertain environment[J].Automation of Electric Power Systems,2020,44(22):134‒142.
ZhouBuxiang, CaiYating, ZangTianlei,et al.Reliability assessment of cyber-physical distribution systems considering cyber disturbances[J].Applied Sciences,2023,13(6):3452. doi:10.3390/app13063452
[26]
ZhengHuankun, TingtingLü, SunYaobin,et al.Reliability analysis of integrated energy cyber physical system considering information equipment failure[J].High Voltage Engineering,2022,48(8):3078‒3087. doi:10.13336/j.1003-6520.hve.20211785
AryaL D, ChoubeS C, AryaR.Differential evolution applied for reliability optimization of radial distribution systems[J].International Journal of Electrical Power & Energy Systems,2011,33(2):271‒277. doi:10.1016/j.ijepes.2010.08.022
[29]
ZhouBuxiang, CaiYating, ZangTianlei,et al.Reliability optimization method for gas-electric integrated energy systems considering cyber-physical interactions[J].Energies,2023,16(13):5187.
[30]
BakkiyarajR A, KumarappanN.Optimal reliability planning for a composite electric power system based on Monte Carlo simulation using particle swarm optimization[J].International Journal of Electrical Power & Energy Systems,2013,47:109‒116. doi:10.1016/j.ijepes.2012.10.055
[31]
王守相,王成山.现代配电系统分析[M].2版.北京:高等教育出版社,2014.
[32]
GuoJing, LiuWenxia, ZhangJianhua,et al.A survey of reliability modeling and evaluation methods for active distribution cyber-physics systems[J].Power System Technology,2019,43(7):2403‒2412.
ChenYangrong, LiJ, XuAng,et al.Reliability evaluation for cyber-physical smart substation[J].Complexity,2021,2021:1‒14. doi:10.1155/2021/3434148
[35]
LiXueming, LiuZengji, TangYi,et al.Reliability analysis of the security and stability control device based on the Monte Carlo method[J].Energy Procedia,2018,145:9‒14. doi:10.1016/j.egypro.2018.04.003
[36]
NiWei, LinLü, XiangYue,et al.Reliability evaluation of integrated energy system based on Markov process Monte Carlo method[J].Power System Technology,2020,44(1):150‒158.
DebK, PratapA, AgarwalS,et al.A fast and elitist multiobjective genetic algorithm:NSGA‒Ⅱ[J].IEEE Transactions on Evolutionary Computation,2002,6(2):182‒197. doi:10.1109/4235.996017
[39]
FonsecaC M, FlemingP J.Genetic algorithms for multiobjective optimization:Formulation,discussion and generalization[C]//Proceedings of the 5th International Conference on Genetic Algorithms(ICGA93).Urbana‒Champaign:Morgan Kaufmann,1993:416‒423.
[40]
CoelloC A C, PulidoG T, LechugaM S.Handling multiple objectives with particle swarm optimization[J].IEEE Transactions on Evolutionary Computation,2004,8(3):256‒279. doi:10.1109/tevc.2004.826067
[41]
MontanoJ, Guzmán‒RodríguezJ P, PalomequeJ M,et al.Comparison of different optimization techniques applied to optimal operation of energy storage systems in standalone and grid-connected direct current microgrids[J].Journal of Energy Storage,2024,96:112708. doi:10.1016/j.est.2024.112708