房建施工中数据中心建筑防火与消防设计研究
Research on Fire Protection and Fire Fighting Design of Data Center Building in Housing Construction
面向高功率密度与高风量并存的数据中心场景,研究构建了以业务连续性为前提的防火与消防设计体系,涵盖基于风险分级的精细化防火分区、针对性洁净气体灭火系统配置、机电联动抑烟控制与独立短捷的应急疏散路径。方法上,提出机房单分区面积不大于1000平方米、复合围护耐火极限不低于3小时,气体灭火采用七氟丙烷并按列区实施分区放气与储瓶冗余,探测采用上下分层与交叉确认,送回风切断与风阀联动,疏散侧设置环形独立通道与沿地低位诱导。以某数据中心为案例验证,改造后火灾响应时间由15秒降至8秒,灭火成功率由85%提升至98%,平均疏散时间由2分钟缩短至1分钟。结果表明,所提策略能在高风速与高负荷耦合条件下实现早期识别、就地控制与安全疏散的协同优化,为数据中心新建与改造提供可复制路径。
Addressing data center scenarios with high power density and high airflow rates, this study establishes a fire prevention and firefighting design framework prioritizing business continuity. The system incorporates risk-based fire compartmentation, customized clean gas fire suppression systems, electromechanical smoke suppression coordination, and independent emergency evacuation routes. Methodologically, the proposed solution specifies: single data center compartments not exceeding 1,000 square meters, composite enclosure fire resistance ratings of at least 3 hours, heptafluoropropane gas fire suppression with zone-specific venting and redundant storage cylinders, multi-layered detection systems with cross-verification, integrated supply-return air cutoff mechanisms with damper linkage, and circular independent evacuation corridors with low-level ground induction. Case validation at a data center demonstrated reduced fire response time from 15 to 8 seconds, improved fire suppression success rate from 85% to 98%, and shortened average evacuation duration from 2 minutes to 1 minute. Results indicate that the proposed strategy achieves synergistic optimization of early detection, localized control, and safe evacuation under high wind speed and load coupling conditions, providing replicable pathways for new data center construction and retrofitting projects.
| [1] |
夏宗军, 李婧, 陈志飞, 李彼, 李晓丹, 刘桂麟. 基于CiteSpace的我国建筑施工期间火灾情况研究[J]. 建筑科学, 2025, 41(05): 176-182. |
| [2] |
陈章迎, 房一泉. 基于智能服务链的数据中心安全架构重构的研究和实践[J]. 通信学报, 2024, 45(S2): 69-73. |
| [3] |
杜宇, 陈达, 朱淼, 吕存浩, 陈洁, 甘亦忻. 既有科研办公楼消防水系统改造难点及相关措施探讨[J]. 给水排水, 2025, 61(05): 105-108. |
| [4] |
于萍, 滕森林, 林志伟. 数据中心机电工程预制化设计的优化方向研究[J]. 中国信息界, 2025,(06): 225-227. |
| [5] |
郭巧洪, 张伟, 付超, 蓝政杰. 基于财务指标体系的数据中心节能改造经济可行性探究[J]. 中国建设信息化, 2025,(12): 74-78. |
/
| 〈 |
|
〉 |