雷击导致西门子7UM622保护装置差动保护误动原因分析
Analysis of the Cause of the Differential Protection Malfunction of Siemens 7UM622 Protection Device Caused by Lightning Strike
进口国际品牌的微机保护为了适应多种系统运行方式,一般对装置的参数都采取开源的方式进行设置,大多数继保工作人员对电量计算的整定值比较重视,而对保护装置配置的系统运行方式可能会忽略,本文通过对深圳某电厂忽略设备系统方式设置导致西门子7UM622保护装置差动保护误动的实例,对西门子保护的参数设置要点进行详细的分析,提出了国际品牌微机保护整定值应增加系统运行方式的设置,可以推广至进口品牌的微机保护参考应用。
To accommodate diverse system operating modes, imported international brand microcomputer protection systems typically adopt open-source parameter configuration. While most relay protection engineers prioritize setting power calculation values, they often overlook system operating mode configurations. This paper analyzes a case where differential protection malfunction occurred in a Siemens 7UM622 device at a Shenzhen power plant due to improper system mode settings in its shunt equipment. The study provides a detailed analysis of key parameter configuration principles for Siemens protection systems, proposing that imported microcomputer protection should incorporate expanded system operating mode configurations. This recommendation can serve as a reference for the application of imported microcomputer protection systems.
/
| 〈 |
|
〉 |